GENERAL |
|
Phase | Single Phase |
Form Factor | Tower |
UPS Topology | Online Double Conversion |
Energy Saving Technology | Online ECO Mode Efficiency > 95% |
Active PFC Compatibility | Yes |
INPUT |
|
Generator Compatibility | Yes |
Nominal Input Voltage ( Vac ) | 230 ± 10% |
Input Voltage Range ( Vac ) | 160 ~ 300 |
Adjustable Voltage Range ( Vac ) | 0~50% Load for 110 ~ 300 Vac 0~60% Load for 120 ~ 300 Vac 0~80% Load for 140 ~ 300 Vac 0~100% Load for 160 ~ 300 Vac |
Input Frequency ( Hz ) | 50 ± 10 60 ± 10 |
Input Frequency Detection | Auto-sensing |
Rated Input Current ( A ) | 4.5 |
Input Power Factor | 0.98 |
Input Connector Type | IEC C14   |
Detachable Power Cord Plug Type | AU x 1   |
Power Cord Length (ft.) | 5.9 |
Power Cord Length (m.) | 1.8 |
OUTPUT |
|
Capacity (VA) | 1000 |
Capacity (Watts) | 900 |
On Battery Waveform | Pure Sine Wave |
On Battery Voltage(s) ( Vac ) | 208 ± 1 % 220 ± 1 % 230 ± 1 % 240 ± 1 % |
Output Voltage Setting | Configurable |
On Battery Frequency ( Hz ) | 50 ± 0.5% 60 ± 0.5% |
Output Frequency Setting | Configurable |
Power Factor | 0.9 |
ECO Mode Voltage Tolerance | ± 15 % |
Overload Protection | Internal Current Limiting, Circuit Breaker, Fuse |
Overload Protection (Line Mode) | 110~120% Load for 1 min, >120% Load Immediately |
Overload Protection (Battery Mode) | 110~120% Load for 10 sec, >120% Load Immediately |
Overload Protection (Bypass Mode) | >130% Load Immediately |
Crest Factor | 3 : 1 |
Harmonic Distortion (Linear Load) | THD<3% |
Harmonic Distortion (Non-linear Load) | THD<5% |
Internal Bypass | Automatic Bypass, Manual Bypass |
Outlet(s) - Total | 4 |
Outlet Type | IEC C13 x 4   |
Outlet(s) - Battery & Surge Protected | 4 |
Typical Transfer Time ( ms ) | 0 |
BATTERY |
|
Runtime at Half Load ( min ) | 15 |
Runtime at Full Load ( min ) | 5 |
Typical Recharge Time ( Hours ) | 5 |
Maximum Charging Current ( A ) | 1 |
Start On Battery | Yes |
Smart Battery Management (SBM) | Yes |
User-replaceable | No |
Battery Type | Sealed Lead-acid |
Compatible Extended Battery Module (EBM) | BPSE36V45A |
Max. EBM Quantity ( pcs ) | 3 |
SURGE PROTECTION & FILTERING |
|
Surge Suppression ( Joules ) | 440 |
EMI/RFI Filtration | Yes |
Phone/Network Protection RJ11/RJ45 (Combo) | 1-in, 1-out |
MANAGEMENT & COMMUNICATIONS |
|
LCD Panel | Yes |
LCD Information Display | Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log |
LCD Setting & Control | Mode Setting, Alarm Setting, Input & Output, Battery Setting |
HID Compliant USB Port(s) | 1 |
Emergency Power Off (EPO) Port | Yes |
Audible Alarms | Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery |
Management Cable ( pcs ) | Power Cord x2, USB Cable x1, Phone Line x1 |
Power Management Software | PowerPanel Business (Recommended) |
PHYSICAL |
|
Enclosure Construction | Metal |
Color | Black |
PHYSICAL SIZE - UPS MODULE |
|
Dimensions (WxHxD) (in.) | 5.94 x 8.86 x 15.51 |
Dimensions (WxHxD) (mm.) | 151 x 225 x 394 |
Weight (lbs.) | 28.88 |
Weight (kg.) | 13.1 |
ENVIRONMENTAL |
|
Operating Temperature (°F) | 32 ~ 104 |
Operating Temperature (°C) | 0 ~ 40 |
Operating Relative Humidity (Non-condensing) ( % ) | 20 ~ 90 |
Operating Elevation ( feet/meters ) | 0-4,921 feet (0-1,500 meters) |
Storage Temperature (°F) | -4 ~ 122 |
Storage Temperature (°C) | -20 ~ 50 |
Storage Relative Humidity (Non-condensing) ( % ) | 10 ~ 90 |
Storage Elevation ( feet/meters ) | 0-4,921 feet (0-1,500 meters) |
Online Thermal Dissipation ( BTU/hr ) | 342 |
Audible Noise at 1.5M from Surface of Unit ( dBA ) | 45 |
CERTIFICATIONS |
|
Certifications | CE, RCM |
RoHS | Yes |